Mon - Fri: 9:00 a.m. - 6:00 p.m.
Language: EN | BM |
WINTERS LE1 High-Volume Pressure Transmitter
WINTERS LE1 High-Volume Pressure Transmitter
WINTERS LE1 High-Volume Pressure Transmitter
WINTERS LE1 High-Volume Pressure Transmitter

Share:


WINTERS LE1 High-Volume Pressure Transmitter

Specifications

LE1: High-Volume Pressure Transmitter

LE1: Low Cost Pressure Transmitter

LE1: General Industry Pressure Transmitter


The WINTERS LE1 High-Volume Pressure Transmitter is a compact transmitter developed for high-volume OEM applications. Its stainless-steel housing, ceramic diaphragm and multiple electrical and mechanical connection options support pump and compressor monitoring, refrigeration and HVAC systems. Available ranges include vacuum and compound measurements as well as positive-pressure ranges up to 5,000 psi.

Key Features

  • Compact SS304 housing with ceramic diaphragm
  • Standard 4–20 mA output with optional voltage output
  • Pressure ranges up to 5,000 psi
  • ±0.5% FSO / ±0.25% BFSL accuracy
  • IP67 enclosure rating
  • CE approved

Engineering Specifications

Specification Details
Pressure ranges Vacuum, compound and positive-pressure ranges; up to 5,000 psi or 250 bar
Output / supply Standard 2-wire 4–20 mA at 12–30 VDC; optional 3-wire 0.5–4.5 VDC at 10–30 VDC
Accuracy ±0.5% FSO / ±0.25% BFSL
Response time Less than 10 ms
Measuring rate 1 kHz
Insulation Greater than 100 MΩ at 50 V
Operating temperature -40°C to 100°C
Compensating / storage temperature -10°C to 80°C / -50°C to 125°C
Pressure port / housing SS304
Wetted parts FKM seal; ceramic diaphragm
Mechanical connection 1/4" NPT standard; 1/4" G optional
Electrical connection Micro connector, Packard connector or cable leads
Protection / approval IP67; CE approved

Selection note: Confirm the pressure range, output signal, supply voltage, electrical connector and process connection before ordering.



 Inquiry - WINTERS LE1 High-Volume Pressure Transmitter